AH500 Programming Manual 
6-244 
D20 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
n=10
Pointer
D0=3 2 1
Source
 
Additional remark: 
1.  If the value in D is less than 0, the instruction is not executed, SM0 is ON, and the error code in 
SR0 is 16#2003. 
2.  If D+n-1 exceeds the device range, the instruction is not executed. SM0 is ON, and the error 
code in SR0 is 16#2003. 
3.  If n is less than 2, or if n is larger than 512, the instruction is not executed, SM0 is ON, and the 
error code in SR0 is 16#200B. 
4.  The instruction SFWR can be used with the instruction SFRD to write and read the data.