Chapter 6 Applied Instructions 
6-273 
API 
Instruction code
Operand  Function 
1206    ZRST  P 
D
1
, D
2
 
Resetting the zone 
Device
X  Y  M  S  T  C  HC  D  L  SM  SR  E  PR  K  16#  “$”  DF
  Pulse instruction
16-bit instruction (5 steps)
32-bit instruction
Symbol: 
D
1
:
Initial device which is reset  Bit/Word 
D
2
:
Final device which is reset  Bit/Word 
Explanation: 
1.  When the instruction is executed, the values in D
1
~D
2
 are cleared. 
2.  When the device number of D
1
 is larger than the device number of D
2
, only D
2
 is reset. 
Example: 
1.  When X0.0 is ON, the auxiliary relays M300~M399 are reset to OFF. 
2.  When X1.0 is ON, the 16-bit counters C0~C127 are reset. (The values of C0~C127 are 
cleared to 0, and the contact and the coil are reset to OFF.) 
3.  When X5.0 is ON, the timers T0~T127 are reset. (The values of T0~T127 are cleared to 0. and 
the contact and the coil are reset to OFF.) 
4.  When X2.0 is ON, the stepping relays S0~S127 are reset to OFF. 
5.  When X3.0 is ON, the output relays Y0.0~Y1.15 are reset to OFF. 
6.  When X4.0 is ON, the 32-bit counters HC0~HC63 are reset. (The values of HC0~HC63 are 
cleared to 0, and the contact and the coil are reset to OFF.)