Chapter 2 Devices
2-27
SM Function
CPU5X0-RS2
CPU5X0-EN
CPU5X1-RS2
CPU5X1-EN
CPU560-EN2
OFF
ON
STOP
RUN
RUN
STOP
Attribute
Default
SM953
An error occurs in Modbus TCP connection 126.
×
*3
×
*5
OFF
R OFF
SM954
An error occurs in Modbus TCP connection 127.
×
*3
×
*5
OFF
R OFF
SM955
An error occurs in Modbus TCP connection 128.
×
*3
×
*5
OFF
R
OFF
SM1000
It is the Ethernet setting flag. When SM1000 is
ON, the data in SR1000~SR1006 is written into
the flash memory.
×
×
-
R/W
OFF
*SM1001
Port1 Ethernet connection status
× × ×
R OFF
*SM1002
Port2 Ethernet connection status
× × × ×
R OFF
*SM1003
Fiber for synchronization connection status
× × × ×
R OFF
*SM1089
MODBUS TCP connection has reached its limit
×
V1.
06
×
V2.
00
OFF
R OFF
SM1090
The TCP connection is busy.
×
×
OFF
R
OFF
SM1091
The UDP connection is busy.
×
×
OFF
R
OFF
SM1100
The network cable is not connected
×
×
OFF
R
OFF
SM1106 Ethernet connection error
×
×
OFF
R OFF
SM1107
HWCONFIG Ethernet─Basic setting,
parameters setting error
×
×
OFF
R OFF
SM1108
HWCONFIG Ethernet─Advanced setting, filter
setting error
×
×
OFF
R OFF
SM1109
HWCONFIG Ethernet─Advanced setting,
TCP/UDP socket─the local port is already
used.
×
×
OFF
R OFF
*SM1112
Email setting error
×
×
OFF
R
OFF
*SM1113
Email service error
×
×
OFF
R
OFF
*SM1116
It is the switch of trigger 1 in the email.
×
×
OFF
R
OFF
*SM1117
Trigger 1 in the email
×
×
OFF
R
OFF
*SM1118
When trigger 1 is triggered but the email cannot
be sent due to the Ethernet connection failure;
SM1118 is ON.
×
×
OFF
R OFF
*SM1119
When trigger 1 is triggered and the email has
been sent successfully; SM1119 is ON.
×
×
OFF
R OFF
*SM1120
When trigger 1 is triggered but the email cannot
be sent due to email content error; SM1120 is
ON.
×
×
OFF
R OFF
*SM1121
When trigger 1 is triggered and the email is
being sent; SM1121 is ON.
×
×
OFF
R OFF
*SM1122
When trigger 1 is triggered and there is an
SMTP server response timeout, SM1122 is ON.
×
×
OFF
R OFF
*SM1123
When trigger 1 is triggered and there is an
SMTP server response error, SM1123 is ON.
×
×
OFF
R OFF
*SM1124
When trigger 1 is triggered and the size of the
attachment exceeds the limit, SM1124 is ON.
×
×
OFF
R OFF
*SM1125
When trigger 1 is triggered and the attachment
is not found, SM1125 is ON.
×
×
OFF
R OFF
*SM1126
It is the switch of trigger 2 in the email.
×
×
OFF
R
OFF
*SM1127
Trigger 2 in the email
×
×
OFF
R
OFF
*SM1128
When trigger 2 is triggered but the email cannot
be sent due to the Ethernet connection failure;
SM1128 is ON.
×
×
OFF
R OFF

Table of Contents