AH500 Programming Manual
6-388
2. When X1.0 is ON, Y0.4~Y0.7 are ON cyclically. It takes twelve scan cycles for Y0.4~Y0.7 to be
ON. After the execution of the instruction is complete, SM693 is ON for a scan cycle.
3. If there is on four-digit seven-segment display, n is within the range between 0 and 3.
After the pins 1, 2, 4, and 8 are connected in parallel, they are connected to Y0.0~Y0.3
on the PLC, and the latches are connected to Y0.4~Y0.7 on the PLC.
When X1.0 is ON, the instruction is executed. Y0.4~Y0.7 are ON cyclically, and the value
in D10 is shown on seven-segment display.
4. If there are two four-digit seven-segment displays, n is within the range between 4 and 7.
After the pins 1, 2, 4, and 8 are connected in parallel, they are connected to Y0.8~Y0.11
on the PLC, and the latches are connected to Y0.4~Y0.7 on the PLC.
The value in D10 is shown on first seven-segment display, and the value in D11 is shown
on second seven-segment display. If the values in D10 and D11 are 1234 and 4321
respectively, 1234 is shown on second seven-segment display.
5. The wiring:
Y0.0 Y0.1 Y0.2 Y0.3 Y0.4 Y0.5 Y0.6 Y0.7 Y0.8 Y0.9 Y0.10 Y0.11
1 2 4 8
10
0
10
1
10
2
10
3
10
3
10
2
10
1
10
0
V+
10
3
10
2
10
1
10
0
V+
1
2
4
8
1
2
4
8
UP
ZP
24VDC
+
Note: The transistor output module AH16AN01T-5A is used in this example.
First 7-segment display
Second 7-segment display
Additional remark:
1. Whether an output is a positive output or a negative output, and whether there is one four-digit
seven-segment display or two four-digit seven-segment displays depend on n.
2. The outputs on the PLC should be NPN transistors whose collectors are open collectors.
Besides, an output has to connect a pull-up resistor to the DC power supply (less than 30 V
DC). Therefore, when an output is ON, a signal of low potential is output.
The negative logic:
Binary-coded
decimal value
(Binary-coded
Signal
3
2
1
0