EasyManua.ls Logo

Delta AH500 - Page 680

Delta AH500
749 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AH500 Programming Manual
6-512
Additional remark:
1. If S
1
or S
2
exceeds the range, the instruction is not executed, SM0 is ON, and the error code in
SR0 is 16#2003.
2. If the data is sent through the TCP socket, and the device from which the data is read is not the
device permitted by the socket, the error occurs, the corresponding error flag is ON, the error
code is 16#6203, and the instruction is not executed. If the number of data sent is larger than
1000, the error occurs, the corresponding error flag is ON, the error code is 16#6204, and the
instruction is not executed. If the devices from which the data is read exceed the device range,
the error occurs, the corresponding error flag is ON, the error code is 16#6205, and the
instruction is not executed.
3. If the data is sent through the UDP socket, and the device from which the data is read is not
the device permitted by the socket, the error occurs, the corresponding error flag is ON, the
error code is 16#620C, and the instruction is not executed. If the number of data sent is larger
than 1000, the error occurs, the corresponding error flag is ON, the error code is 16#620D, and
the instruction is not executed. If the devices from which the data is read exceed the device
range, the error occurs, the corresponding error flag is ON, the error code is 16#620E, and the
instruction is not executed.
4. If the data is sent through the UPD socket, and the remote communication port number is 0,
the error occurs, the corresponding error flag is ON, the error code is 16#620B, and the
instruction is not executed.
5. During the transmission, if the computer as the client abandons the connection, the error
occurs, the corresponding error flag is ON, and the error code is 16#6214. During the
transmission, if there is a response timeout, the error occurs, the corresponding error flag is
ON, and the error code is 16#6212.
6. When executing this instruction, if the network cable is not connected, SM1100 will be ON and
the error code is 16#600D.