AH500 Programming Manual 
7-6 
Error code  Description 
CPU 
Status 
ERROR 
16#2010 
1. The instruction does not support the device. 
2. Encoding error 
3. The instruction is a 16-bit instruction, but 
the constant operand is a 32-bit code. 
(SM5) 
Stop  Blinking  Keep 
The number of operands is incorrect. (SM5) 
Incorrect division operation (SM0/SM5). 
16#2013 
The value exceeds the range of values which 
can be represented by the floating-point 
Self-defined
Blinking 
Keep
 
16#2014 
The task designated by TKON/YKOFF is 
incorrect, or exceeds the range. (SM5) 
Stop  Blinking 
Keep
 
16#2015 
There are more than 32 levels of nested 
program structures supported by CALL. (SM0) 
Self-defined
Blinking 
Keep
 
16#2016 
There are more than 32 levels of nested 
program structures supported by FOR/NEXT. 
Self-defined
Blinking 
Keep
 
16#2017 
The number of times FOR is used is different 
from the number of times NEXT is used. 
Stop  Blinking 
Keep
 
16#2018 
There is a label after FEND, but there is no 
SRET. 
There is SRET, but there is no label. (SM5) 
Stop  Blinking 
Keep
 
The interrupt task is not after FEND. (SM5) 
IRET/SRET is not after FEND. (SM5) 
16#201B 
There is an interrupt task, but there is no 
IRET. 
There is IRET, but there is not interrupt task. 
(SM5) 
Stop  Blinking 
Keep
 
End is not at the end of the program. (SM5) 
There is CALL, but there is no MAR. (SM5) 
16#201E 
The function code used in MODRW is 
incorrect. (SM102/SM103) 
Self-defined
Blinking 
Keep
 
16#201F 
The length of the data set in MODRW is 
incorrect. (SM102/SM103) 
Self-defined
Blinking 
Keep
 
16#2020 
The communication command received by 
using MODRW is incorrect. (SM102/SM103) 
Self-defined
Blinking 
Keep
 
16#2021 
The checksum of the command received is 
incorrect. (SM102/SM103) 
Self-defined
Blinking 
Keep
 
16#2022 
The format of the command used in MODRW 
does not conform to the ASCII format. 
Self-defined
Blinking 
Keep
 
16#2023 
There is a communication timeout when 
MODRW is executed. (SM120/SM103) 
Self-defined
Blinking 
Keep
 
16#2024 
The setting value of the communication 
timeout is invalid. (SM120/SM103) 
Self-defined
Blinking 
Keep
 
16#2025 
There is a communication timeout when RS is 
executed. (SM120/SM103) 
Self-defined
Blinking 
Keep
 
The interrupt number used in RS is incorrect. 
16#2027 
The execution of FWD is abnormal. 
(SM102/103) 
Self-defined
Blinking  Keep