Chapter 4 Parameters
VFD-EL-W 
4-99 
 
01.09  Accel. Time 1  0.1–600.0 / 0.01–600.00 sec.  10.0  0.5  0.5  Adjusts according 
to customer’s 
applications 
01.10  Decel. Time 1  0.1–600.0 / 0.01–600.00 sec. 
10.0  5.0  5.0 
01.12  Decel. Time 2  0.1–600.0 / 0.01–600.00 sec.  10.0  3.0  3.0 
The time the AC 
motor drive 
decelerates to 
stop when the 
pressure reaches 
the setting value.
 
Parameter
Function  Settings  Default
End 
user’s 
master
End 
user’s 
slave
Note 
02.00 
First Master 
Frequency 
Command Source 
0: Digital keypad UP/DOWN 
keys or Multi-function Inputs 
UP/DOWN. 
1: 0–10 V from AVI 
2: 4–20 mA from ACI 
3: RS-485 (RJ45) 
communication 
4: Digital keypad potentiometer
0  2  2 
Adjusts according 
to customer’s 
applications 
02.01 
First Operation 
Command Source 
0: Digital keypad 
0  0  0 
Adjusts according 
to customer’s 
applications 
1: External terminals. Keypad 
STOP/RESET enabled. 
2: External terminals. Keypad 
STOP/RESET disabled. 
3: RS-485 communication. 
Keypad STOP/RESET 
enabled. 
4: RS-485 communication. 
Keypad STOP/RESET 
disabled.