Chapter 4 Parameters
VFD-EL-W 
4-100 
 
Parameter
Function  Settings  Default
End 
user’s 
master
End 
user’s 
slave
Note 
10.00 
PID Set Point 
Selection 
0: Disable 
1: Digital keypad UP/DOWN 
keys 
2: Reserved 
3: Reserved 
4: PID set point (Pr.10.11) 
0  1  1 
Adjusts according 
to customer’s 
applications 
10.01 
Input Terminal for 
PID Feedback 
0: Positive PID feedback from 
external terminal AVI  
(0–10 V
DC
) 
1: Negative PID feedback from 
external terminal AVI  
(0–10 V
DC
)  
2: Positive PID feedback from 
external terminal ACI  
(4–20 mA)  
3: Negative PID feedback from 
external terminal ACI  
(4–20 mA)  
0  3  3 
 
10.02 
Proportional Gain 
(P) 
0.0–10.0  1.0  1.2  1.2 
Adjusts according 
to customer’s 
applications 
10.03  Integral Time (I) 
0.00–100.00 sec. 
(0.00=Disable) 
1.00  0.7  0.7 
10.04  Differential Time (D)
0.00–1.00 sec. 
0.00 
-  - 
 
10.12  PID Deviation Level
0.0–100.0%  10.0  5  5 
When the 
is < 0.5 kg and 
time > 15 sec., 
follow the settings 
for Pr.10.20. 
10.13 
PID Deviation 
Detection Time 
0.1–300.0 sec.  5.0  15  15 
10.18 
Feedback of PID 
Physical Quantity 
Value 
1.0–99.9  99.9  10  10 
feedback of PID 
physical quantity 
value to be 10 kg. 
10.19 
PID Calculation 
Mode Selection 
0: Serial mode 
1: Parallel mode 
0  1  1 
The parallel PID 
calculation mode 
applies for the 
constant pressure 
water supply 
control. 
10.20 
Erroneous PID 
Feedback Deviation 
Level Action 
0: Wan and keep operating 
1: Warn and coast to stop 
2: Warn and ramp to stop 
3: Ramp to stop and restart 
after Pr.10.21 delay time 
0  3  3 
When there is 
water shortage or 
unusual pressure 
feedback, the 
pump stops 
running for 1800 
sec. (30 minutes) 
until the pressure 
feedback is back 
to normal. 
10.21 
Restart Delay Time 
after Erroneous PID 
Deviation Level   
0–9999 sec.  60  1800
1800