Chapter 4 Parameters
VFD-EL-W 
4-21 
 
Explanation  Settings  Default  Customer
10.20 
Erroneous PID Feedback 
Deviation Level Action 
0: Warn and keep operating  
1: Warn and coast to stop 
2: Warn and ramp to stop 
3: Ramp to stop and restart after Pr.10.21  
   delay time (No display of error and  
   warning) 
4: Ramp to stop and restart after Pr.10.21  
delay time. The number of times of restart 
  is limited by Pr.10.50 (Number of Times of  
Restart after PID Fault). 
0 
 
10.21 
Restart Delay Time after 
Erroneous PID Deviation 
Level   
0–9999 sec.  60 
 
10.22
Set Point Deviation Level  0–100%  0   
10.23
Detection Time of Set 
Point Deviation Level 
0–9999 sec.  10 
 
10.24
Deviation Level of Liquid 
Leakage 
0–50%  0 
 
10.25
Liquid Leakage Change 
Detection 
0–100% (0: disable)  0 
 
10.26
Time Setting for Liquid 
Leakage Change 
0.1–10.0 sec. (0: disable)  0.5 
 
10.35 
Multi-Pump Control 
Mode 
0: Disable 
1: Fixed Time Circulation (alternative 
operation) 
2: Fixed quantity control (multi-pump 
operating at constant pressure) 
0 
 
10.36  Multi-pump ID 
0: Multi-pump control mode is disabled 
1: Master 
2–4: Slave 
0 
 
10.37
Multi-pump’s Fixed Time 
Circulation Period 
1–65535 (minute)  60 
 
10.38
Frequency to Start 
Switching Pumps 
0.00 Hz–Fmax  60.00 
 
10.39
Time Detected When 
Pump Reaches the 
Starting Frequency 
0.0–3600.0 sec.  1 
 
10.40
Frequency to Stop 
Switching Pumps 
0.00 Hz–Fmax  48.00 
 
10.41
Time Detected When 
Pump Reaches the 
Stopping Frequency 
0.0–3600.0 (sec.)  1.0 
 
10.42
Pump’s Frequency at Time-
out (Disconnection) 
0.00 Hz–Fmax  0.00 
 
10.43  Pump’s Error Treatment 
bit0: Determines whether the erroneous pump 
switches to an alternative pump when an 
error occurs in the running pump 
0: All pumps stop 
1: Switch to an alternative pump 
1