Chapter 4 Parameters
VFD-EL-W 
4-22 
 
Explanation  Settings  Default  Customer
bit1: Determines the erroneous pump to be in 
a standby or stop status after reset 
0: Set the erroneous pump to be in a standby 
status after reset 
1: Set the erroneous pump to be in a stop 
status after reset 
 
bit2: Determines whether the master pump 
received the RUN command or not when 
an error occurs in the running pump 
0: When an error occurs in the running pump, 
the master pump does not receive the RUN 
command 
1: When an error occurs in the running pump, 
the master pump can choose to run with an 
alternative pump, instead of the erroneous 
pump 
 
10.44 
Selection of Pump’s Start-
up Sequence 
0: By pump ID # 
1: By running time. 
1 
 
10.45
Running Time of Multi- 
pump Under Alternative 
Operation 
0.0–360.0 sec.  60.0 
 
10.49
Specify the Setting for 
Pr.10.12 [PID Deviation 
Level] 
0: Use the existing setting (default), and 
check for any error per the feedback 
deviation  
1: Set the low water pressure percentage (%), 
and check for any error per the physical 
quantity feedback. 
0 
 
10.50
Number of Times of 
Restart after PID Fault 
0–1000 times  0