EasyManua.ls Logo

DENT Instruments ELITEpro XC - Appendix E-Calculated Power Channel Formulas; Wye Configuration L1-N, L2-N, L3-N

DENT Instruments ELITEpro XC
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
115
Appendix ECalculated Power Channel Formulas
The following information details the formulas used to calculate the parameters available in the Power
Sum Channels 5 and 6.
WYE CONFIGURATION L1-N, L2-N, L3-N
Measurement Formula Notes/Description
Amps (System)
L1 + L2 + L3
3
Average of L1, L2, and L3 amp values.
Volts (System )
Sum of three phase to neutral voltages
3
For a Phase to Neutral with WYE
configured meter.
Average of the three phase-to-neutral
voltages.
kW (System) L1 kW + L2 kW + L3 kW
Sum of L1, L2, and L3 phase watt
values.
kWh (System)
L1 kW + L2 kW + L3 kW
# of samples in an hour
Calculated per waveform sample with
a running total of each waveform kWh
for the integration period.
VAR (System) L1 kVAR + L2 kVAR + L3 kVAR
VARh (System)
L1 kVAR + L2 kVAR + L3 kVAR
# of samples in an hour
See kWh (System) WYE notes.
VA (System) L1 kVA + L2 kVA + L3 kVA
VAh (System)
L1 kVA + L2 kVA + L3 kVA
# of samples in an hour
See kWh (System) WYE notes.
Apparent PF System
kW System
kVA System
Measurement calculation information
is provided for reference only.
Displacement PF System
kW System
SQRT [(kW System)
2
+ (kVAR System)
2
]
w ww. . com