To measure outputs pulse:
1) To count pulses, connect the wires of your measurement device to the +/- connection points on the
ELITEpro SP.
NOTE: You can open ELOG 15, and ensure that your PC and logger time are synchronized by selecting
Logger > Logger Clock > Synchronize Time to Match PC.
2) Using an existing setup table (or follow the steps in Section 2 of this manual to create a new one),
turn on the Digital 1 and/or Digital 2 channels.
3) Enter a descriptive identifier in the Name field. Choose your Power Channel to measure, the desired
option from the Value drop-down list, and enter a scaling factor in the Scale field.
4) Click SEND SETUP TABLE to Logger.
NOTE: When logging is turned on or a new setup table is sent, pulse outputs start at the integration
period relative to the hour that logging starts. For example, if you have a 5 minute integration period
and you turn logging on at 1:05:01 PM (5 minutes and 1 second after the hour), logging AND pulse
output accumulation will NOT start until 1:10:00 PM.
5) Upon completion of your pulse output measurements, disconnect the wires of your device.
w ww. . com
information@itm.com1.800.561.8187

Table of Contents

Other manuals for DENT Instruments ELITEpro XC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DENT Instruments ELITEpro XC and is the answer not in the manual?

DENT Instruments ELITEpro XC Specifications

General IconGeneral
BrandDENT Instruments
ModelELITEpro XC
CategoryData Loggers
LanguageEnglish