Current Transformers Recommended CT Phase Shift Values
Clamp On CT-CON-0150EZ
CT-CON-1000
1.10°
0.20°
Split Core Small CT-SCS-0050
CT-SCS-0100
2.20°
2.20°
Split Core
Medium
CT-SCM-0100
CT-SCM-0200
CT-SCM-0400
CT-SCM-0600
1.75°
1.50°
1.30°
1.30°
Split Core Large CT-SCL-0600
CT-SCL-1000
0.00°
0.00°
Split Core High
Accuracy
CT
SHS
0005
CT
SHS
0015
0.50°
0.50°
Hinge Mini CT-HSC-020
CT-HSAC-050
0.75°
0.75°
Hinge MIDI CT-HMC-0100
CT-HMC-0200
0.12°
0.30°
Revenue Grade
Toroidal Solid
Core
CT-RGT12-0005
CT-RGT12-0020
CT-RGT12-0050
CT-RGT12-0100
0.00°
0.00°
0.00°
0.00°
Revenue Grade
Split Core
CT-SRS-005
CT-SRS-050
CT-SRL-100
CT-SRL-200
CT-SRL-400
-0.10°
-0.23°
0.06°
0.06°
-0.06°
Recommended CT Phase Shift Values
3) Click OK.
4) Check the Enable THD checkbox if you want total harmonic distortion to appear as a percentage in
the Data File Summary report. Selecting this option automatically populates any required value field
necessary to determine distortion.
Once the Quick Setup is completed, the View Typical Setup button appears in the Quick Setup area of
the screen. Clicking this button displays a wiring diagram showing how to connect the CTs and the
voltage leads of the ELITEpro XC corresponding to the selected setup. The diagram can be printed and
carried into the field for easy reference during installation. Refer to ELOG Quick Setup Wiring Diagrams
for detailed information of each Quick Setup option.