700271-0001 Rev. G 05/13 17
5 System Programming
5.1 UL 864 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to
comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, certain programming features or options must be limited to
specific values or not used at all as indicated below.
Program feature or
option
Permitted in UL864?
(Y/N)
Possible settings Settings permitted in
UL864
Function #1, Setting
#3 - Alarm Code
Rounds
Y 1-4 Rounds 3 or 4 Rounds
5.2 4x4+1 Keypad
FUNC – Use to select Function to view or modify.
ENTER – Press ENTER to save new setting.
CLR – Press to silence beeper or to clear entry on the display.

Table of Contents