System Programming Digitize Inc.
28 700271-0001 Rev. G 05/13
5.5.5 Setting 5 Low Battery Restore Code Rounds
This function sets the number of times a Low Battery Box Number & Low Battery Restore
Code will be sent when the panel returns from a Low Battery condition to a Normal
Condition. The number of rounds can be set from 0 to 4. If the rounds is set equal to 0, no
transmission will occur.
Default Setting: Low Battery Restore Rounds: 0 Rounds
5.6 Function 3 AC Fail Settings
5.6.1 Setting 1 AC Fail Box Number
The DET-16 panel can be programmed to send an independent box number when it detects
an AC Fail Condition. The box number can be up to 8 digits long.
Default Setting: AC Fail Box Number: 125
5.6.2 Setting 2 AC Fail Code
When the DET-16 panel detects an AC Fail condition, it will transmit an AC Fail Box
Number followed by the AC Fail Code. The AC Fail Code can be set from 0 – 9.
Default Setting: AC Fail Code: 2
5.6.3 Setting 3 AC Fail Rounds
This function sets the number of times an AC Fail Box Number & Code will be sent when an
AC Fail condition is detected. The number of rounds can be set from 0 to 4. If the rounds is
set equal to 0, no transmission will occur.