5.4.7 Setting 7 Zone Alarm Restore Code Rounds
This function sets the number of times a Zone Box Number & Alarm Restore Code will be
sent when a zone that was previously in Alarm returns to a Secure condition. The number of
rounds can be set from 0 to 4. If the rounds is set equal to 0, no transmission will occur when
the zone returns to secure status.
Default Setting: For ALL Zones: 0 Rounds
5.4.8 Setting 8 Zone Trouble Restore Code
The DET-16 sends a Trouble Restore Transmission when a zone that was previously in a
Trouble condition returns to a Secure condition. Each zone of the DET-16 panel can be
programmed with a completely independent Trouble Restore Code. The Zone Trouble
Restore Code can be set from 0 – 9. When a Trouble Restoral is sent, the DET-16 will first
transmit the box number followed by the Zone Trouble Restore Code. For example: Zone 1
returns to a Secure condition after previously being in Trouble, the panel would send 22221.
The 1 is the trouble restore code.
Default Settings:
Zone 1 1 Zone 9 1
Zone 2 2 Zone 10 2
Zone 3 3 Zone 11 3
Zone 4 4 Zone 12 4