Digitize Inc. System Programming
700271-0001 Rev. G 05/13 21
Zone 1 1 Zone 9 1
Zone 2 2 Zone 10 2
Zone 3 3 Zone 11 3
Zone 4 4 Zone 12 4
Zone 5 5 Zone 13 5
Zone 6 6 Zone 14 6
Zone 7 7 Zone 15 7
Zone 8 8 Zone 16 8
5.4.5 Setting 5 Zone Trouble Code Rounds
This function sets the number of times a Zone Box Number & Trouble Code will be sent
when a zone is placed in a TROUBLE condition. The number of rounds can be set from 0 to
4. If the rounds is set equal to 0, no transmission will occur when the zone is placed in
trouble.
Default Settings: For ALL Zones: 0 Rounds
5.4.6 Setting 6 Zone Alarm Restore Code
The DET-16 sends an Alarm Restore Transmission when a zone that was previously in an
Alarm condition returns to a Secure condition. Each zone of the DET-16 panel can be
programmed with a completely independent Alarm Restore Code. The Zone Alarm Restore
Code can be set from 0 9. When an Alarm Restoral is sent, the DET-16 will first transmit
the box number followed by the Zone Alarm Restore Code. For example: Zone 1 returns to a
Secure condition after previously being in Alarm, the panel would send 22221. The “1” is the
alarm restore code.
Default Settings:
Zone 1 1 Zone 9 1
Zone 2 2 Zone 10 2