Digitize Inc. System Programming
700271-0001 Rev. G 05/13 29
Default Setting: AC Fail Rounds: 1 Round.
5.6.4 Setting 4 AC Fail Restore Code
The DET-16 sends an AC Fail Restore Transmission when the panel goes from an AC Fail
condition to a Normal Operating condition. The AC Fail Restore Code can be set from 0 9.
When the AC Line voltage returns to a normal condition, the DET-16 will first transmit the
box number followed by the AC Fail Restore Code.
Default Setting: AC Fail Restore Code: 2
5.6.5 Setting 5 AC Fail Restore Code Rounds
This function sets the number of times an AC Fail Box Number & AC Fail Restore Code will
be sent when the panel returns from an AC Fail condition to a Normal Condition. The
number of rounds can be set from 0 to 4. If the rounds is set equal to 0, no transmission will
occur.
Default Setting: AC Fail Restore Rounds: 0 Rounds
5.7 Function 4 Transmission Speed
The speed of transmission is adjustable over a range from 1/8 (.125) to four (4.000) seconds.
Default Setting: Transmission Speed: .250 Seconds (1/4 second)