Default Settings: For ALL Zones: Enabled
5.4.16 Setting 16 Allow Restore Preemption
When enabled, if this zone becomes restored it will allow any Alarm or Trouble to preempt
the telegraph transmission of this restored zone. This setting is factory set and should only be
changed with careful consideration.
Default Settings: For ALL Zones: Enabled
5.4.17 Setting 17 Zones: Normally Open / Normally Closed
Each zone can be independently programmed to monitor Normally Open or Normally Closed
contacts.
Default Settings: For ALL Zones: Normally Open
5.4.18 Setting 18 Zone Priority
The Priority for each of the 16 zones can be independently programmed from 0 to 15. Zones
with a higher priority level and the proper settings will preempt zones with a lower priority.
Zones with a higher priority level will be removed first from the queue when transmitting.
The factory setting is Zone 1 the highest priority, zone 16 the lowest.
Default Settings:
Zone 1 0 Zone 9 8