Digitize Inc. System Programming
700271-0001 Rev. G 05/13 23
Zone 5 5 Zone 13 5
Zone 6 6 Zone 14 6
Zone 7 7 Zone 15 7
Zone 8 8 Zone 16 8
5.4.9 Setting 9 Zone Trouble Restore Code Rounds
This function sets the number of times a Zone Box Number & Trouble Restore Code will be
sent when a zone that was previously in Trouble returns to a Secure condition. The number
of rounds can be set from 0 to 4. If the rounds is set equal to 0, no transmission will occur
when the zone returns to a Secure condition.
Default Settings: For ALL Zones: 0 Rounds
5.4.10 Setting 10 Disable / Enable Zones
Each of the 16 zones on the DET-16 panel can be disabled. Tripping a disabled zone will not
start a telegraph transmission.
Default Settings: For ALL Zones: Enabled
5.4.11 Setting 11 Preempt Troubles
When enabled, if this zone goes into Trouble it can preempt the telegraph transmission of
another zone in Trouble with a lower Priority level. This setting is factory set and should
only be changed with careful consideration.
Default Settings: For ALL Zones: Enabled