System Programming Digitize Inc.
24 700271-0001 Rev. G 05/13
5.4.12 Setting 12 Preempt Alarms
When enabled, if this zone goes into Alarm it can preempt the telegraph transmission of
another zone in Alarm with a lower Priority Setting or any zone in Trouble. This setting is
factory set and should only be changed with careful consideration.
Default Settings: For ALL Zones: Enabled
5.4.13 Setting 13 Preempt Power
When enabled, if this zone goes into Alarm, it will preempt the telegraph transmission of a
Low Battery or AC Fail condition. This setting is factory set and should only be changed
with careful consideration.
Default Settings: For ALL Zones: Enabled
5.4.14 Setting 14 Allow Alarm Preemption
When enabled, if this zone goes into Alarm, it will allow another zone in Alarm with a
higher Priority Level to preempt the telegraph transmission of this zone. This setting is
factory set and should only be changed with careful consideration.
Default Settings: For ALL Zones: Enabled
5.4.15 Setting 15 Allow Trouble Preemption
When enabled, if this zone goes into Trouble, it will allow another zone in a Trouble state
with a higher Priority Level or any zone in Alarm to preempt the telegraph transmission of
this zone. This setting is factory set and should only be changed with careful consideration.