39
EN
IP2348EN
Emergency Unit Monitoring (00÷02)
The emergency unit will be tested by shutting of the power to
the control panel and open the door with the emergency unit.
The test is never done in operation mode selection OPEN and
normally not in OFF, unless parameter 37 “Emergency Action
In OFF Mode” is set to On, see below. Authorities can demand
that the emergency unit is monitored on a regular
basis, see parameter 40 “Emergency Unit Test Interval” below.
Half an hour before this time has elapsed the following outer
impulse generates an emergency opening test . If there is no
outer impulse within the next half hour, the operator control unit
generates the opening impulse by it self (ghost impulse). The
test is also always performed after a Reset and after changing
operation mode selection from a position where a test is not
done to a position where the test is made.
00= Off.
01= Convenience monitoring. Is a simpler one-channel moni-
toring. Convenience monitoring can be used for monitoring
battery. If the DAS901BAT1 battery is used, see parameter 43.
02= Redundant monitoring. Is a redundant two-channel mo-
nitoring that is a demand for escape route according to:
EN16005 or DIN18650.
NOTE: on DAS200TRF set to 02.
(DAS200TRG)
Partial Open Position (00-99%)
Sets the “winter opening” size.
NOTE: A building is certified for a certain COW. Depending on
how many people that is allowed to be in the specific area
there also has to be a certain opening width. Partial open
position must be set to 80% of the certified distance in
escape routes.
(DAS200T/TRF)
(DAS200TRG)
Opening direction (00÷01)
00= 1 wing Right.
01= 1 wing Left or 2 wings.
NOTE: On DAS200TRG this parameter cannot be selected, the
opening direction is defined with the position of the belt
attachment bracket.
Hold force (00÷60 N)
Adjustment of the force used to keep the door in closed position.
Run Program (01÷05)
Performance adjustment. Sets how fast or slow the door shall
accelerate or break.
01= Smooth, for light doors.
05= Max Performance. For heavy doors.
Inner Impulse (motion) Monitoring (00÷01)
According to EN 16005 or DIN18650 it is a demand to have Inner
impulse monitoring = On in escape routes.
00= Disables monitoring.
01= Enables monitoring.
*NOTE: on DAS200TRF set to 01.
NOTE: If the Configuration Tool CT is used, disable the “learn
access”:
Learn AccessMMI Read accessMMI Write access
AUTOMATIC
(DAS200TRG)
Partial Hold Open Time (00÷60s)
Hold open time for Inner & Outer impulses with operation mode
selection PARTIAL and for the Nurse impulse.
Push & Go Hold Open Time (00÷60s)
Hold open time after a Push&Go.