dormakaba ED900 Setup and Troubleshooting Instructions Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Power reserve module SVP-PR test.
-
Test off
. SVP-PR power reserve module test is performed once every hours, or
minutes after AC power has been turned on. In event of an error:
• Unlocking is not performed and no automatic door movements are initiated.
• Error code E is displayed, See Appendix B, troubleshooting error codes.
. SVP-PR power reserve module can be used but must be tested on a regular
basis if using:
• SVP- DCW emergency escape motor lock with automatic latching action.
• M-SVP DCW emergency escape lock.
. Test is automatically activated if a fire protection module is recognized in
conjunction with SVP- DCW or M-SVP DCW locks.
TS
Static force in opening direction.
. Static force in opening direction (basic parameter for wind load control). Static force
on door closing edge can be changed using this parameter.
. Internal monitoring system checks if parameter setting is admissible. If setting exceeds
admissible value, the setting is alternately displayed with the permissible value.
. After parameter set, verify setting meets ANSI/BHMA standard A. (low energy).
See Chapter .
Parameter
setting *
N - N
. lb f - . lb f
Static force in closing direction.
. Static force in closing direction (basic parameter for wind load control). Static force on
door closing edge can be changed using this parameter.
. Internal monitoring system checks if parameter setting is admissible. If setting exceeds
admissible value, the setting is alternately displayed with the permissible value.
. After parameter set, verify setting meets ANSI/BHMA standard A. (low energy).
See Chapter .
Parameter
setting *
N - N
. lb f - . lb f
*
Motor driven latching action, automatic
mode.
. System offers a motor driven latching action in automatic mode in addition to
mechanical latching action.
. The EP parameter setting is designed to increase static force on door to insure proper
closing despite resistance caused by door seals or locking devices.
. Setting should be increased step by step from a low setting so as to avoid damage to
the system. Use the lowest possible setting.
. Ensure that both the door itself and the arm or track installation are suitable for the
additional, permanent forces.
-
Motor driven latching action angle.
Door opening angle at which motor driven latching action EP is activated.
• Starting angle of the latching angle adjustable from °.
- °
Keep closed force.
-
Off
to
. Keep closed force is:
• Permanently applied following motor drive latching action.
• Designed to keep door in closed position even if wind acts on door.
. Keep closed force can be set from (off) to , maximum force.
A.. Driving parameters detail.