Half/Pack
®
Issued April 2018
Body Controller Software
Copyright 2018, Heil Environmental
Printed in the U.S.A.
Body Controller Software
124
B
Pump On
Activated
N/A
ON
C
Reverse
Activated
N/A
ON
D
Turn Signal
Deactivated
N/A
OFF
Note: The Strobe light circuit-2 can be turned ON in following conditions:
With Pump ON or Reverse signal activated or Strobe switch ON
If the unit is configured with Whelen strobes, the strobes are ON in the above conditions
with Turn signal being deactivated.
G07 Output Function -- Top Door Close (Body Output %QX0.06)
This output function controls the Top Door Close output.
Condition
Modifiable Parameters
Default Setting
A
None
N/A
Conditions Necessary to activate the circuit:
Condition
Function or Component
Status
I/O Address
Status
A
Top Door Close Push
Button
Activated
CAN
ON
B
and Pump On
Activated
N/A
ON
Note: This signal is energized using a CAN based control by energizing the Top Door Close switch either from Street side
or from Curb side panel. With Conditions (A AND B) true, will activate the Top Door Close output.
G08 Output Function -- Top Door Open (Body Output %QX0.05)
This output function controls the Top Door Open output.
Condition
Modifiable Parameters
Default Setting
A
None
N/A
Conditions Necessary to activate the circuit:
Condition
Function or Component
Status
I/O Address
Status
A
Top Door Open Push
Button
Activated
CAN
ON
B
and Pump On
Activated
N/A
ON
Note: This signal is energized using a CAN based control by energizing the Top Door Open switch either from Street side
or from Curb side panel. With condition (A AND B) true, will activate the Top Door Open output signal.
G09 Output Function – Container Light Circuit (In Cab Output %QX128.11)
This circuit operates the Container light circuit. Here CAN control is used to turn ON/OFF the
Container Light Circuit either from Street side or from the Curb side of a dual control panel unit.
Condition
Modifiable Parameters
Default Setting