Field Description
Protocol
Select one of the three:
Gilbarco: To permit the GVR TLS350 protocol commands.If the “i” button that comes into view is
selected when a Gilbarco POS connection has been mapped, the supported VeederRoot commands will
be shown.
DOMS OPC: To permit the DOMS OPC protocol commands.
PV4: To permit the OPW PV4 protocol commands.
Probe Emulation: Emulation of the "M" command of the Progauge probe (the console responds to
the M command). This protocol can be used by forecourt controllers that support the Progauge probe M
command and need to get information on the product height, water height and product temperature only.
Port
If serial communication was selected above, select which serial port will be used (COM1 or COM2).
If TCP-IP communication was selected above, configure the TCP-IP port that to be used.
Baud rate /
Parity / Data
bits / Stop bits
Theses fields are in operation if serial communication has been selected. Configure the settings for the
serial ports.
Printer
Connection
Select:
None: If no printer is connected
USB: If a printer is connected through the USB port.
COM1/COM2: If a printer is connected to the serial port (baud rate for the printer should be set to
9600 bps). Note that this is necessary for the fields to become available if the serial ports have not been
configured for POS/FCC communication.
Gilbarco
Invalid Field
Character
Select the symbol (“?” or “0”) to use in the VeederRoot protocol commands for invalid fields. The default
is “?”.
Click Save and Apply settings to console when you complete the Protocols tab configuration.
6.1.4 Tank Group
NOTE: The number of tanks are configured in the Site Info tab. Tank parameters are
configured in Tanks setup from the Main Menu.
This tab is used to make Siphon (Manifold) groups.
IMPORTANT: Tanks in a Siphon (Manifold) group must contain the same product.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 25