9. Alarm status: Select the method that will cause an alarm:
l Open: For normally open sensors, the alarm is caused when the sensor contact closes.
l Closed: For normally closed sensors, the alarm is caused when the sensor contact opens.
NOTE: The ProGauge on/off and discriminating operate as normally closed sensors.
10. Select the Location (Tank number) of the sensor.
11. Click Save to save the Settings configuration.
7.1.1 OPW FMS smart sensors (model LX Plus only).
OPW-FMS Smart Sensors are automatically detected and will come into view next to the “+” sign in the
header. The sensor type and serial number will show automatically on the relevant fields (fields 3,5).
To configure the sensor:
1. Make sure the applicable sensor is selected in the header. Enter a number for the sensor to identify
the sensor in the configuration.
2. Push the Enable button. If the sensor is not enabled (and the button is "grayed-out") the system
cannot read the sensor status (but the sensor configuration can continue to be saved).
3. The Sensor Type will automatically show when the sensor is detected.
4. Enter a name for the sensor
5. The Serial Number will automatically show when the sensor is detected.
6. Select a Location from the drop-down. This is used for information only.
Click Save to save the Settings configuration.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 52