6.3.7.1 Leak Test Setup
On the Tanks Setup tab, click on the applicable tank. Configure the parameters as shown:
1. Select the Leak Test tab.
2. Put the slider button into Enabled status.
3. Select the frequency of the test (Daily, Weekly, Monthly, Yearly).
4. Leak test warning period in days: This warning is in use when the user has selected the weekly,
monthly or yearly frequency for an automatic test. If the console has not completed a Ieak test within x
number of days in the frequency period, this warning will show to warn the user.
EXAMPLE: If Weekly auto test frequency is selected and the Warning period = 6 days. If after 6
days from the start of the week the console has not completed a leak test, a warning will show to
notify the user.
5. Duration (mins): This is how long the test will run. The minimum is 30 mins. It is recommended to set
this parameter to 120 mins.
6. Minimum fill (%): This is the minimum fill in the tank for a leak test to start. If the fill in the tank is less
than this threshold, the leak test will not start. It is recommended to set this parameter to 50%.
7. Leak test threshold (liters per hour): The minimum is 1 gallon per hour (3.785 liters per hour) for
XMT-SI probes and for DMP-IS probes with 1 temperature sensor. For DMP probes with 5
temperature sensors and for OPW 924B probes the threshold can be 0.2 gph or 0.1 gph.
8. Push Save to save this configuration
For a Scheduled Test, select a date from the date picker, then configure the parameters as above.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 46