6.3.8 ACR mode
The menu in the image below will show when the tank is in ACR Mode.
6.3.8.1 ACR Configuration Parameters
l Unstable delivery timer: Enter the time necessary to let the product settle at the end of delivery.
Turbulence can occur during and after a delivery. This can cause incorrect indications. Enter a time
from 0 (disable) to 59 minutes. After this time a probe can be monitored as usual.
The recommended value is five (5) minutes.
l Start delivery detection: This shows the minimum quantity of product increase necessary to start
delivery detection. The recommended value is 100 liters.
l End delivery detection: This is the quantity (in gallons/liters) for each minute to show the end of
delivery. The recommended value is 20 liters (5.25 gallons).
l Vapor Recovery system:
l Evaporation factor (%): This is used only when ACR tank mode is selected to calculate evaporation
loss as a percentage of unit volume. For diesel products enter “0,” for unleaded products enter “0.17.”
6.3.8.2 Calibration Parameters
l Number of segments: The tank is divided into a specified number of segments for Autocalibration.
The permitted range is 25-45 segments. The higher number of segments selected, the more precision
in the Autocalibration. This would also increase the time to complete Autocalibration.
l Low segment: This shows the lowest segment of the calibration range.
l High segment: This shows the top segment of the calibration range.