6.3.3 Density
Configure a probe with an installed density float in this screen. The parameters that show in the illustration
above are only available when the DMP Density Probe type is selected in " T a n k Set u p M e n u " o n
p a g e 3 3 > " S e t t i n g s " on p a g e 3 3 .
1. Select Density from the configurations parameters. The Product family and the Product density
TC are shown.
2. Enter the Tolerance. Accepted values are between 1-100. This is used to set the accepted
tolerance of measured density. Whenever the measurement is outside of this tolerance, the
system will use the default Product density TC value for all calculations. The default value is 20%.
3. Current Density Values: The density values as read by the sensor.
l Density: This is the density value at ambient temperature
l TC density: This is the density value compensated at reference temperature.
l Temperature: This is the current temperature of the product
4. The Coefficients settings are values that are given with the density sensor.
a. Enter the Coefficient A (negative) and Coefficient B (positive) values in the fields.
b. Click Save after you enter the values.
5. Density (hydrometer) / TC Density (hydrometer): If the density of the product can be measured
with a 3rd party instrument such as a hydrometer, then the density value as measured by the
instrument can be used to calibrate the density sensor. Use either of the two values to calibrate the
density sensor (the system will automatically change the B value to adapt to the manually entered
hydrometer density.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 38