l Calibration cycles max: This is the maximum calibration cycles value parameter. This sets the
number of auto calibration cycles in which the segments will not be changed if the auto calibration
process is not complete. the minimum value is 5 and the maximum is 10.
l Calibration cycles required: This value specifies the Autocalibration status percentage (%).
When each segment of the specified auto calibration volume range is at this value, Autocalibration is
complete. Because there can be segments in an Autocalibration cycle that are not changed, some
segments can be changed more than the required value.
6.3.9 ACR Results
The graphic shows the reference chart (entered by the user) and the autocalibration chart.
1. The Reference straptable and Calculated straptable buttons control which of the two straptables to
use for the current volume conversions. When autocalibration is complete, the user must select one of
the two buttons to use the “Reference” table or to use the “Autocalibration” table.
2. The Cold reset button will delete all data (autocalibration table and number of calibrations) and the
procedure will start again.
3. The Soft reset button will delete the number of calibrations but will keep the autocalibration table. This
lets the user improve the autocalibration if the autocalibrated data is not sufficient.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 49