6.3.10 Reconciliation
l Test vend: This is the quantity of product used in the calibration of hose meters. In meter calibration,
there is a product quantity removed from the tank without a related sale. if Unaccounted variance is
greater than Test vend threshold, then it is reported as “Test vend” and it is not thought of as a “Loss”.
l Unexpected sales (liters): An alarm will be caused when the tank is in a quiet mode (there are no
sales) and product loss is sensed.
l Average time: This specifies the time for the loss warning or loss alarm.
l Loss warning (liters): A difference more than this threshold will cause a Loss Warning
l Loss alarm (liters): A difference more than this threshold will cause a Loss Alarm.
l Unaccounted variance (%): If a difference in the daily reconciliation is more than this threshold, it will
cause an alarm.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 50