For all other probes types, enter the product density at the reference temperature. Values are permitted in
API format or in Kg/m3 format.
6.3.4 AEF (Aqueous Ethanol Float) Thresholds
When an AEF is selected in the Water detection type, the AEF thresholds screen will show as a separate tab.
NOTE: The water height will not be shown if the Delivery status is “In progress”. During a
delivery, the AEF reading is discarded and alarms will not occur to avoid incorrect
measurements.
6.3.4.1 For Progauge Probes with AEF
The AEF in a Progauge probe measures very precise water levels at the bottom of the tank. The setup
screen is shown in the image below:
Four (4) thresholds will show that will must be calculated. The current AEF reading value is used by the
console to automatically make these calculations.
l T2: AEF position in normal product
l t2: AEF position when lift begins in ethanol (phase separation has started)
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 39