l Pump sales: The quantity of liters that were sold by the tank (as recorded by the dispensers).
l Test vend: The quantity of fuel that was pumped out of the tank during a pump calibration check.
l Operating var (variance): This is the difference between Tank Depletion and Pump Sales, In liters and
as a % of tank sales.
l Temp var (variance): This is a temperature difference for the given time period.
l Evap var (Evaporation variance): This is an evaporation difference for the given time period.
l Water var (variance): This is a difference because of a change in the water volume for the given time
period.
l Pump calib (calibration): This is a difference because of the dispenser meter drift (this is only
applicable if a meter offset has been programmed in the Site Mapping).
l Theft: This is a difference that was recorded as a theft (it will be necessary for the Unexpected Sales
threshold to be programmed in the Reconciliation settings in the Tank Setup).
l Unaccounted var (variance): This is calculated as:
n Unaccounted variance = Operating variance Temp variance Evap variance Water
variance - Pump calibration Theft.
n This is calculated in liters and as a percent of sales.
11.12 Configuration
A summary of the configuration is given in this menu. Click the PRINT button to print the configuration report
to a printer connected to the PC.
Use the three (3) relay slider buttons (“Print Tanks Relays,”Print Sensors Relays,” “Print LLDs Relays") to
include relay configurations for the different modules.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 73