Section 7 Sensor Setup
7.1 ProGauge Sensors
To add a ProGauge sensor:
1. Tap the + sign to add a new sensor.
2. Enter a Sensor Id number (e.g. 1, 2, 3 etc.).
3. When the Enabled button is on (blue), the sensor is enabled in the system. To disable a sensor, tap
this button again so it is "grayed-out." The sensor's configuration will stay but alarm conditions cannot
be caused.
4. Select a Sensor Type from the drop-down:
l On/off: ProGauge sensor with one float only.
l Discriminating: ProGauge sensor with two floats. One float that can sense product and one float
to sense water.
l 2 Ch Wireless sensor: ProGauge wireless RF sensor with two floats (product, water).
l 1 Ch Wireless sensor: ProGauge wireless RF sensor with one float (product).
l Other selections refer to OPW-FMS Smart Sensors (for the LX Plus model only).
5. Enter a Name for the sensor (up to 30 characters).
6. Compliance:Put the button in the ON (blue) position if youwant the sensor to be part of the
Compliance reporting. The sensor compliance feature is a way to see the report for specified sensors
for 3 periods: Today, Last 24 Hours and Last 12 Months (or selected date).
7. Position of Product / Position of Water: This field is enabled only when a ProGauge discriminating
sensor has been selected. The user must give a slot number on the CN10 connector or on the input
card of the MagLink I/O
8. Sensor Channel: This is applicable only when a ProGauge On/off or Discriminating sensor has been
selected. Select where the sensor is to be connected. Internal refers to the internal CN10 connector
(only EXd sensors can connect to the CN10). For Intrinsically Safe sensors, select the MagLink I/O.
M2051_r4 MagLink LX 4 and LX Plus Configuration Manual | Dover Fueling Solutions 51