l If “Water level from probe + water offset” > Water Min Float level, the Water volume
and Water level will be shown.
l If “Water level from probe + water offset” < Water Min Float level, the Water volume will
not be shown but the Water level will be shown.
m. Move the Fast delivery QACRslider button to the right (to the enabled position) to let the
application use the QACR algorithm for the delivery detection. Set the delivery time (in
minutes). The QACR algorithm is the delivery algorithm that is usually used when the tank
is in ACR mode. For some situations where a tank is in Standard mode and the site would
like to have the delivery report as quickly as possible, the QACR algorithm can be used.
n. Enter the Delivery time in minutes: Set the delivery time to tell the console how much time
to wait from the moment the delivery detection has ended before the final delivery report is
printed. This delivery time is used to permit time for the turbulence within the tank to settle
and to have a stable level.
o. Enter the amount (in liters) to Start delivery detection: Set the Delivery start threshold to
tell the console when to know when a delivery has started (for example if set at 300 liters,
this means that as soon as there is a 300 liter volume increase, then this is a delivery start
point).
Click Save when you complete the Settings configuration.
6.3.2 Thresholds
1. Select Thresholds from the configurations parameters. Use one of two methods to adjust each of
the parameter values:
a. Move the slider until you get the correct values.