11. Drill or punch holes for the cable
glands on the plate used for
cable entry.
Do the work while the plate is
outside the UPS cabinet to
prevent metal shavings or chips
from entering into electronics.
12. Install suitable cable glands on
the plate.
13. Route all cables through the wire way to the UPS terminal blocks.
14. Reinstall the wire entry plate
and install conduit if needed.
15. Connect power wiring to the terminals and tighten to the right torque.
See Table
14
.
16. When all power wiring is complete, reinstall the safety shield panels.
17. For installing the control wiring,
use the communication cable
conduit to route the cables to
the communication terminals.
If you install a parallel system, repeat the above steps to all units in the system.