Figure 41. Options for relay outputs configuration
7. Enter the code(s) of the function(s) that you want to trigger the relay when
they become active.
8. Press OK and Save to save the changes.
Figure 42. Entering the codes of the functions that will trigger the relay
9. If you selected one of the MiniSlots, these default values are available:
• Relay 1: #262 On Line (LED is lit)
• Relay 2: #260 On Battery (LED is lit)
• Relay 3: #352 Alarm (LED is lit)
• Relay 4: #261 On Bypass (LED is lit)
• Relay 5: #15 Low Battery warning
Alternatively, you can configure the relays with any event you want.
Eaton 93PM UPS 30–200 kVA
User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 86 (126)