UPS Operating Instructions
Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality 6-13
6.2.8 System Controls
Tap the CONTROLS tab on the main menu navigation bar to display the Controls screen. Double conversion
operation, transfer to bypass, shutdown, and charger control commands are controlled through this screen. In
addition, the screen displays the current status of the UPS.
Table 6-4 describes the control functions and provides instructions to access and use the command menu
screens.
Table 6-5 lists the typical System Status Screen Messages that are displayed during UPS operation.
For UPS operating instructions using the System Controls, see paragraph 6.3 or 6.4.
Figure 6-16 through Figure 6-20 show the major control screens.
Figure 6-16. Typical System Control Screen
Table 6-4. Controls Menu Operation
Function Subfunction Operation
System Controls The CONTROLS tab on the main menu navigation bar displays the System Controls
screen.
System Status GO ONLINE starts the UPS in Double Conversion mode or transfers the UPS to Double
Conversion mode from Bypass mode.
Bypass GO TO BYPASS starts the UPS in Bypass mode or transfers the UPS to Bypass mode from
Double Conversion mode.
Charger TURN ON CHARGER/TURN OFF CHARGER sets the battery charger on or off.
Battery Test RUN BATTERY TEST starts the battery test.
Table 6-5. Typical System Status Messages
Function Message
UPS Double Conversion; Bypass; ESS
Bypass Off; On; Available
Charger Charger Resting; Charger