UPS Installation Plan and Unpacking
Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality 3-21
Table 3-8. Power Cable Conduit Recommendations for the Eaton 93PM-100-2 and Eaton 93PM-100-3 (N+1)
UPS Model UPS Rating Voltage Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
60 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
41-1/21
AC Output (Three Wire)
(A, B, C, Ground)
41-1/41
DC
Battery
(Positive, Negative, Ground)
52-1/21
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
70 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
421
AC Output (Three Wire)
(A, B, C, Ground)
41-1/21
DC
Battery
(Positive, Negative, Ground)
52-1/21
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
80 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
421
AC Output (Three Wire)
(A, B, C, Ground)
41-1/21
DC
Battery
(Positive, Negative, Ground)
52-1/21
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
90 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
421
AC Output (Three Wire)
(A, B, C, Ground)
421
DC
Battery
(Positive, Negative, Ground)
52-1/21
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
100 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
421
AC Output (Three Wire)
(A, B, C, Ground)
421
DC
Battery
(Positive, Negative, Ground)
52-1/21
NOTE Wires per conduit include ground wire.