UPS Installation Plan and Unpacking
3-24 Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality
There is no manual DC disconnect device within the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is
computed based on 2 volts per cell.
External DC input overcurrent protection and disconnect switch is to be supplied by the customer. Table 3-11
and Table 3-12 list the maximum ratings for continuous-duty rated circuit breakers satisfying the criteria for
both. Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For
longer discharge times a larger disconnect may be required.
Table 3-11. Recommended DC Input Battery Disconnect Circuit Breaker Ratings (216 Cell)
Output Rating
UPS Model UPS Rating 480V
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
20 kW 100% Rated 60A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
30 kW 100% Rated 90A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
40 kW 100% Rated 125A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
50 kW 100% Rated 150A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
60 kW 100% Rated 200A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
70 kW
100% Rated 225A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
80 kW 100% Rated 250A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
90 kW
100% Rated 300A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
100 kW 100% Rated 300A