UPS Installation Plan and Unpacking
3-18 Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality
Table 3-5. Input/Output Ratings and External Wiring Recommendations for the Eaton 93PM-100-2 and 93PM-100-3 (N+1)
Basic Unit Rating
Units Rating 50/60 Hz
kW 60 70 80 90 100
Input and Output Voltage Volts 480/480 480/480 480/480 480/480 480/480
AC Input to UPS Rectifier (0.99 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps 94 108 120 133 146
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
1/0
(1)
2/0
(1)
2/0
(1)
3/0
(1)
4/0
(1)
Minimum Conductor Size (Ground)
Number
AWG or kcmil
(each)
6
(1)
6
(1)
6
(1)
6
(1)
6
(1)
AC Input to UPS Bypass (Three Wire, Dual-Feed)
Full Load Current
(3) Phases, (1) Ground
B
Amps 94 108 120 133 146
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
1/0
(1)
2/0
(1)
2/0
(1)
3/0
(1)
4/0
(1)
Minimum Conductor Size (Ground)
Number
AWG or kcmil
(each)
6
(1)
6
(1)
6
(1)
6
(1)
6
(1)
DC Input from External Battery (Line-Up-and-Match
Eaton 93PM IBC)
(1) Positive, (1) Negative, (1) Ground
C
Total Amps (216 cell)
Total Amps (240 cell)
149
134
174
156
198
178
223
200
247
223
Minimum Conductor Size (Phase Positive and Negative)
Number per Pole
AWG or kcmil
(each)
2/0
(1)
See Note
2/0
(1)
See Note
2/0
(1)
See Note
2/0
(1)
See Note
2/0
(1)
See Note
Minimum Conductor Size (Ground)
Number
AWG or kcmil
(each)
4
(1)
4
(1)
4
(1)
4
(1)
4
(1)
DC Input from External Battery (Standalone Eaton 93PM
IBC)
(1) Positive, (1) Negative, (1) Ground
C
Total Amps (216 cell)
Total Amps (240 cell)
149
134
174
156
198
178
223
200
247
223
Minimum Conductor Size (Phase Positive and Negative)
Number per Pole
AWG or kcmil
(each)
3/0
(2)
3/0
(2)
3/0
(2)
3/0
(2)
3/0
(2)
Minimum Conductor Size (Ground)
Number
AWG or kcmil
(each)
4
(1)
4
(1)
4
(1)
4
(1)
4
(1)
AC Output to Critical Load (Three Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps 72 84 96 108 120
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
2
(1)
1
(1)
1/0
(1)
2/0
(1)
2/0
(1)
Minimum Conductor Size (Ground)
Number
AWG or kcmil
(each)
6
(1)
6
(1)
6
(1)
6
(1)
6
(1)
NOTE Callout letters A, B, C and D map to Figure 5-10 through Figure 5-17.
NOTE Line-up-and-match battery wiring with a 105°C
rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet (IBC).