UPS Installation Plan and Unpacking
3-16 Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality
Figure 3-9. 93PM External Parallel Wire Length
NOTE Required parallel system wiring length must be equal to ensure approximately equal current sharing when in Bypass mode. For
proper operation the following must be true:
1A = 2A = 3A = 4A
1B = 2B = 3B = 4B
NOTE Any difference in wire length will result in decreased capacity of the UPS system while on bypass. For example, a 10% difference
between the longest and shortest wire lengths will result in a decrease in bypass capacity of 10%.
Bypass Input to UPS Units
UPS 1
Battery
UPS 2
UPS 3
UPS 4
Output from UPS Units
Battery
Battery
Battery
1A
2A
3A
4A
1B
2B
3B
4B