UPS Installation Plan and Unpacking
3-4 Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality
The UPS equipment operating environment must meet the weight requirements shown in Table 3-2 and the
size requirements shown in Figure 3-1 through Figure 3-8. Dimensions are in millimeters (inches).
NOTE Refer to the Eaton 93PM Sidecar Integrated Accessory Cabinet-Tie and Tie Bypass
(50 kW and 100 kW SIAC-T, and 50 kW and 100 kW SIAC-TB) Installation and
Operation Manual, listed in paragraph 1.8, for Sidecar Integrated Accessory
Cabinet-Tie (SIAC-T) and Sidecar Integrated Accessory Cabinet-Tie Bypass
(SIAC-TB) weight and size requirements.
Table 3-2. UPS Cabinet Weights
Model
Weight
kg (lb)
Frame Shipping Installed Point Loading
Eaton 93PM-100-1
Capacity 357 (786) 337 (743) 4 at 84 (186)
Redundant 363 (799) 343 (756) 4 at 86 (189)
Eaton 93PM-100-2
Capacity 414 (912) 394 (869) 4 at 98 (217)
Redundant 426 (939) 406 (896) 4 at 102 (224)
Eaton 93PM-100-3 Redundant 490 (1080) 470 (1037) 4 at 118 (259)
Eaton 93PM-100-1 with UPS Top Entry Wiring Sidecar (no breakers)
Capacity 429 (944) 406 (894) 4 at 102 (224)
Redundant 434 (957) 411 (907) 4 at 103 (227)
Eaton 93PM-100-2 with UPS Top Entry Wiring Sidecar (no breakers)
Capacity 492 (1084) 469 (1034) 4 at 117 (259)
Redundant 498 (1097) 475 (1047) 4 at 119 (262)
Eaton 93PM-100-3 with UPS Top Entry Wiring Sidecar (no breakers) Redundant 562 (1238) 539 (1188) 4 at 135 (297)
Eaton 93PM-100-1 with four breaker Left-Mounted or Right-Mounted
Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B)
Capacity 457 (1005) 433 (954) 4 at 108 (239)
Redundant 463 (1018) 439 (967) 4 at 110 (242)
Eaton 93PM-100-2 with four breaker
Left-Mounted or Right-Mounted SIAC-B
Capacity 520 (1145) 496 (1094) 5 at 99 (219)
Redundant 526 (1158) 502 (1107) 4 at 126 (277)
Eaton 93PM-100-3 with four breaker
Left-Mounted or Right-Mounted SIAC-B
Redundant 590 (1299) 566 (1248) 4 at 142 (312)
UPS Top Entry Wiring Sidecar (no breakers) — — 74 (162) —
Four breaker SIAC-B — — 106 (233) —