UPS Installation Plan and Unpacking
3-20 Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 3-7 or Table 3-8 for
conduit recommendations.
Per NEC article 300, 3(B), all three-phase conductors must be run in the same conduit. A ground wire must be
run in the same conduit as the phase conductors.
When running parallel wires in multiple conduits a ground wire must be run in each conduit in accordance with
NEC Table 250.122.
Conduit is sized to accommodate one ground conductor per conduit, sized in accordance with
NEC Table 250.122.
Conduit sizes listed are for copper wiring only.
Table 3-7. Power Cable Conduit Recommendations for the Eaton 93PM-100-1 and Eaton 93PM-100-2 (N+1)
UPS Model UPS Rating Voltage Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
20 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
43/41
AC Output (Three Wire)
(A, B, C, Ground)
43/41
DC
Battery
(Positive, Negative, Ground)
52-1/21
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1))
30 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
41-1/41
AC Output (Three Wire)
(A, B, C, Ground)
411
DC
Battery
(Positive, Negative, Ground)
52-1/21
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
40 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
41-1/41
AC Output (Three Wire)
(A, B, C, Ground)
41-1/41
DC
Battery
(Positive, Negative, Ground)
52-1/21
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
50 kW
480 Vac
AC Input to UPS Rectifier and Bypass
(A, B, C, Ground)
41-1/41
AC Output (Three Wire)
(A, B, C, Ground)
41-1/41
DC
Battery
(Positive, Negative, Ground)
52-1/21
NOTE Wires per conduit include ground wire.