UPS Installation Plan and Unpacking
Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality 3-25
Table 3-12. Recommended DC Input Battery Disconnect Circuit Breaker Ratings (240 Cell)
Output Rating
UPS Model UPS Rating 480V
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
20 kW 100% Rated 60A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
30 kW 100% Rated 90A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
40 kW 100% Rated 125A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
50 kW 100% Rated 150A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
60 kW 100% Rated 175A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
70 kW
100% Rated 200A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
80 kW 100% Rated 225A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
90 kW
100% Rated 250A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
100 kW 100% Rated 300A