UPS Installation Plan and Unpacking
Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 6 www.eaton.com/powerquality 3-19
The power wiring terminals are pressure terminations, UL and CSA rated. See Table 3-6 for external power
cable terminations.
Figure 4-7 and Figure 4-8 show the location of the UPS power cable terminals.
Table 3-6. UPS External Power Cable Terminations for the Eaton 93PM-100-1, 93PM-100-2, and 93PM-100-3
Terminal Function Terminal Function
Number and Size of Pressure
Termination
AWG or kcmil
Tightening Torque
Nm (lb in)
Screw Size and Type
AC Input to UPS Rectifier E1 Phase A 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
E2 Phase B 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
E3 Phase C 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
AC Input to Bypass E6 Phase A 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
E7 Phase B 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
E8 Phase C 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
AC Output to Critical Load E9 Phase A 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
E10 Phase B 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
E11 Phase C 2 - #6-250 kcmil 22.6 (200) 1/4" Hex
DC Input from Battery E4 Battery (+) 4 - #6-250 kcmil 22.6 (200) 1/4" Hex
E5 Battery (-) 4 - #6-250 kcmil 22.6 (200) 1/4" Hex
Customer Ground Ground Ground 6 - #14-1/0 5.1 (45) Slotted
NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3-7 or Table 3-8.