Eaton 93PR Series - Figure 4-11. CAN and Pull-Chain Wiring for Parallel UPP Without Mobs

Eaton 93PR Series
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25-75 kW
User's and Installation Guide
49
10
9
10
9
10
9
11
12
11
12
11
12
Figure 4-11: CAN and Pull-Chain Wiring for Parallel UPP Without MOBs
NOTE
NCandNOdesignationsonMOBAUXcontactsaredefinedwithbreakerinOFF(open)position.IfMOBcontacts
havepigtailleads,usethesamewiregaugetoconnecttotheUPPandusethecorrectcrimpconnectionsforthe
wiregauge.ExternalCANconnectionsbetweenUPPcabinetsrequireshieldedtwistedpairwire.Usetwistedpair
wiringbetweentheUPPandMOBAUXcontacts.Alwaysconfirmcontactoperationpriortowiring.