EasyManua.ls Logo

Eaton 93PR Series - Installing Eaton Sync Control; Figure 4-12. Sync Control TB1 Terminal Location

Eaton 93PR Series
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25-75 kW
User's and Installation Guide
50
4.5.4 Installing Eaton Sync Control
Refer to the operating instructions provided with the
Eaton
Sync Control.
TB1
UPS System−A – Bypass Voltage Phase A
UPS System−A – Bypass Voltage Phase B Return
UPS System−A – Bypass Voltage Phase B
UPS System−A – Bypass Voltage Neutral
UPS System−B – Bypass Voltage Phase A
UPS System−B – Bypass Voltage Phase B
UPS System−B – Bypass Voltage Neutral
UPS System−B – Bypass Voltage Phase B Return
UPS System−A – Output Voltage Phase A
UPS System−A – Output Voltage Phase B
UPS System−A – Output Voltage Neutral
UPS System−B – Output Voltage Phase A
UPS System−B – Output Voltage Phase B
UPS System−B – Output Voltage Neutral
On Bypass Common
UPS System−A – On Bypass NO
UPS System−B – On Bypass NO
UPS System−A – Building Alarm 1 (see Note)
UPS System−A – Building Alarm 1 Return
UPS System−B – Building Alarm 1 (see Note)
UPS System−B – Building Alarm 1 Return
Jumper
Common Return
UPS System−A – Active Master Source
UPS System−B – Active Master Source
UPS System−A – Synchronized to Load B
UPS System−B – Synchronized to Load A
Load Sync Enabled
Common Return
Figure 4-12: Sync Control TB1 Terminal Location

Table of Contents

Other manuals for Eaton 93PR Series

Related product manuals