Web Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 5 92
7. To set whether an outlet state (On, Off, or Reboot) can be changed, check or uncheck the Enable
Switching check box, then click Save.
l
Disabled: Uncheck the check box to disable the setting, which indicates that the outlet state cannot be
changed.
l
Enabled: Check the check box to enable the setting, which indicates that the outlet state can be
changed.
8. To set the state of the outlet with the ePDU is powered on, select one of the following values from the
State on Device Startup drop-down list, then click Save:
l
On: The outlet is powered after a duration of time set in the Outlet Switch On After field.
l
Off: The outlet is not powered.
l
Last Known State: The outlet is powered on if it was On when the ePDU was powered Off.
Otherwise, the outlet is not powered.
9. Administrator or User with Read/Write/Control only. To specify the duration an outlet will be Off
before switching On during a reboot, type the number of seconds the outlet should be Off in the Power
Reboot Period(s) text box. Click Save.
10. To enter new threshold values, type new values in any of the text boxes that follow, then click Save:
l
Low warning current threshold
l
High warning current threshold
l
High critical current threshold
11. To reset the threshold values to the default values, click Default, then click Save.
12. To reset a kilowatt hour (kWh) counter to zero, click Reset kWh, then click Save.
Environment
Configure Environment Sensor Settings
1. Access the Web interface and log in.
2. Under Power Management, select Environment. The Environment page displays.
3. In the Environment panel, review the present ePDU environment monitoring temperature and humidity
data. Also review the status of installed dry contacts, open or closed.
NOTE This setting can be overwritten by the Power Reboot Period defined for groups of
outlets on the Group Settings dialog.
NOTE The environmental monitoring data panel only displays data under these
circumstances:
l
if the EMP is installed and configured in the system
l
if the user read-write access rights