Installation
Eaton ePDU G3 Operation Manual P-164000277—Rev 5 26
Figure 23. Single Rearward
4. Remove the existing screws in the holes where you want to position the bracket in the U-Channel rail.
5. Align the bracket screw holes with the U-Channel screw holes and secure the bracket (with clip feet
installed) to the rack rail with the U-Channel screws.
6. Repeat for the second bracket.
7. Snap the ePDU into the mounting clip feet. When you hear a clicking sound for each mounting clip foot,
the ePDU is secure.
8. Continue to “Grounding the ePDU” on page 28 if you are installing a ground screw and grounding cable.
Otherwise, go to “Network and Environmental Ports” on page 29.
Installing the Horizontal Models in a Rack Cabinet
10-32 Screw
8-32 Screw
keps Nut
keps Nut
Mount the ePDU on the front of the clip foot.
NOTE: The outlets will be facing out the back of the ePDU.
Back of
Bracket
NOTE For horizontal installations in square-hole racks, a cage nut must be installed in the
selected mounting holes.